Description:DIN rail, Type 2 /Class Ⅱwith high duty MOVs for use in system at boundaries from LPZ 0B -1 and higher.
Feature:
● Uniform current flow technology for MOV
● Non-destructive screening technology for MOV
● High discharge capacity
● Capable of protecting terminal equipment
● Visual and remote status indication
● Multifunctional terminals for connecting conductors and busbars
● DIN rail installation
Part Number | RL385-80W2-31R | RL385-100W2-31R |
Nominal Voltage (Un) | 230/400Vac | 230/400Vac |
Max. continuous operating voltage (Uc) | 385Vac(L-N),260Vac(N-PE) | 385Vac(L-N),260Vac(N-PE |
Nominal discharge current (8/20 µs) (In) | 40kA | 50kA |
Max.discharge surge current (8/20μs) | 80kA | 100kA |
Voltage protection level (Up) | 1.6kV(L-N),1.5(N-PE) | 1.8kV(L-N),1.5(N-PE) |
Voltage protection level for 5kA (Up) | 1.2kV | 1.2kV |
Response time (tA) | ≤25ns | ≤25ns |
Short circuit withstand capability | 25kArms | 25kArms |
Temporary overvoltage (TOV) (Ut) | 440V/5s | 440V/5s |
Max. overcurrent protection | ≤200A gL/gG | ≤200A gL/gG |
TOV characteristic | Withstand | Withstand |
Approval | CE | CE |
Part Number | RL385-120W2-31R |
Nominal Voltage (Un) | 230/400Vac |
Max. continuous operating voltage (Uc) | 385Vac(L-N),260Vac(N-PE) |
Nominal discharge current (8/20 µs) (In) | 60kA |
Max.discharge surge current (8/20μs) | 120kA |
Voltage protection level (Up) | 1.8kV(L-N),1.5(N-PE) |
Voltage protection level for 5kA (Up) | 1.2kV |
Response time (tA) | ≤25ns |
Short circuit withstand capability | 25kArms |
Temporary overvoltage (TOV) (Ut) | 440V/5s |
Max. overcurrent protection | ≤200A gL/gG |
TOV characteristic | Withstand |
Approval | CE |