Description:DIN rail, combined Type 1 & 2/ClassⅠ& Ⅱwith CDGG technology for use in TN-S、TT power supply network system at boundaries from LPZ 0A-2.
Feature:
● CDGG Technology
● High discharge capacity
● Capable of protection terminal equipment
● Multifunctional terminals for connecting conductors and busbars
● DIN rail installation
Part Number | RL260-25W1-31 |
Nominal Voltage (Un) | 230/400Vac |
Max. continuous operating voltage (Uc) | 260Vac(L-N),260Vac(N-PE) |
Nominal discharge current (8/20 µs) (In) | 25kA(L-N),100kA(N-PE) |
Lightning impulse current (10/350 µs) (limp) | 25kA(L-N),100kA(N-PE) |
Specific energy(W/R) | 156.25KJ/ohms(L-N),2500KJ/ohms(N-PE) |
Charge | 12.5As(l-N),50As(N-PE) |
Follow current extinguishing capability (If i) | 10kArms |
Voltage protection level (Up) | 2.0kV |
Voltage protection level for 5kA (Up) | 1.0kV |
Response time (tA) | ≤100ns |
Short-circuit withstand capability(Iscw) | 10kArms |
Temporary overvoltage (TOV) (Ut) | 440V/5s |
Max. overcurrent protection | ≤250A gL/gG |
TOV characteristic | Withstand |