Description:DIN rail, Type 1 & Type 2/ClassⅠ&Class ⅡSPD with anti-vibration pluggable module for use in 230/400Vac TN-S system at boundaries from LPZ 0A -1 and higher.
Features:
● MOV&CDGG Technology
● Non-follow current
● High discharge capacity
● Capable of protection terminal equipment
● Visual and remote status indication
● Multifunctional terminals for connecting conductors and busbars
● DIN rail installation
| Part Number | RV600-25W1-10R | RV600-25W1-10 |
| Max.PV voltage (Ucpv) | 600Vdc | 600Vdc |
| Nominal discharge current (8/20 µs) (In) | 25kA | 25kA |
| Lightning impulse current (10/350 µs) | 25kA | 25kA |
| Specific energy(W/R) | 156.25KJ/Ω | 156.25KJ/Ω |
| Charge | 12.5As | 12.5As |
| Voltage protection level (Up) | 3.6kV | 3.6kV |
| Voltage protection level for 5kA (Up) | 2.5kv | 2.5kV |
| Response time (tA) | ≤100ns | ≤100ns |
| Max. overcurrent protection | ≤250A gL/gG | ≤250A gL/gG |
| Short-circuit withstand capability (ISCPV) | 1000Arms | 1000Arms |
| Approval | CE | CE |
| Part Number | RV1000-25W1-10R |
| Max.PV voltage (Ucpv) | 1000Vdc |
| Nominal discharge current (8/20 µs) (In) | 25kA |
| Lightning impulse current (10/350 µs) | 25kA |
| Specific energy(W/R) | 156.25KJ/Ω |
| Charge | 12.5As |
| Voltage protection level (Up) | 4.0kV |
| Voltage protection level for 5kA (Up) | 2.5kv |
| Response time (tA) | ≤100ns |
| Max. overcurrent protection | ≤250A gL/gG |
| Short-circuit withstand capability (ISCPV) | 1000Arms |
| Approval | CE |